Application:
Used in control, monitoring circuits, and protection lines with rated voltage 450/750V and below.
Manufacturing Standard
This product is manufactured in accordance with the Chinese National Standards GB/T 9330.2-2008 and GB/T 9330.3-2008.
Scope of Application
Voltage Rating: Suitable for rated voltage 450/750V and below
Product Specifications: 2–61 cores, 1.5–10 mm²
Operating Characteristics
Power frequency rated voltage (U₀/U): 450/750V.
Maximum allowable long-term operating temperature of the conductor: 70°C.
Ambient temperature during cable installation: not lower than 0°C.
Recommended minimum bending radius:
For unarmored cables: not less than 6 times the cable outer diameter.
For armored or copper tape shielded cables: not less than 12 times the cable outer diameter.
For shielded flexible cables: not less than 6 times the cable outer diameter.