Coal Mine Power Cable

Application:
Used in coal mine power distribution systems or industrial installations in the coal mining industry.

Production Standard
This product is manufactured in accordance with the enterprise standard MT/T 818.13-2009.

 

 

Application Industry

Operating Characteristics

  1. Rated power frequency voltage U₀/U: 1.8/3kV.

  2. Maximum allowable operating temperature of the conductor: 90°C.

  3. Short-circuit condition: The maximum conductor temperature shall not exceed 250°C and the duration shall not exceed 5 seconds.

  4. Installation temperature: The ambient temperature during cable laying shall not be lower than 0°C.

  5. Minimum bending radius:

    • Three-core cable: Not less than 15 times the outer diameter of the cable.

    • Single-core cable: Not less than 21 times the outer diameter of the cable.

 