PVC-Insulated PVC-Sheathed Control Cable for Coal Mines

Application:
Used in coal mining industrial installations for control, monitoring, and protection circuits with a rated voltage of 450/750V and below.

Production Standard
This product is manufactured in accordance with the following enterprise and industry standards:
MT/T 386-2011, Q/YT 001-2015, MT/T 386-2011, Q/YT 012-2019.

Application Industry

Operating Characteristics

  1. Power frequency rated voltage (U₀/U): 450/750V.

  2. Maximum allowable long-term conductor temperature: 70°C.

  3. Ambient temperature during installation: not lower than 0°C.

  4. Recommended minimum bending radius:

    • Unarmored cables: not less than 6 times the cable outer diameter.

    • Armored or copper tape shielded cables: not less than 12 times the cable outer diameter.

    • Shielded flexible cables: not less than 6 times the cable outer diameter