Manufacturing Standard
This product is manufactured in accordance with the Chinese National Standard GB5023 (1997).
This standard is equivalent to the International Electrotechnical Commission (IEC) Standard IEC 227 (1993).
Scope of Application
This product is suitable for fixed installation in power equipment with a rated voltage of U/U 450/750V and below.
Operating Characteristics
Operating temperature: Under normal operation, the maximum conductor temperature is either 70°C or 90°C.
Installation temperature: The ambient temperature during cable installation shall not be lower than 0°C.
Bending radius:
For cables with an outer diameter (D) less than 25 mm, the minimum allowable bending radius is 4D.
For cables with an outer diameter (D) equal to or greater than 25 mm, the minimum allowable bending radius is 6D.
Note: Our company also manufactures the JB8734 series of wiring cables.